Eberle DIN-Rail Thermostats and Control Sets
Eberle DIN-rail thermostats are control units that manage snow and ice melting and frost protection heating automatically.

A heating control panel starts and stops the heating cable automatically according to weather and surface conditions.
Richtpreis ab Werk Istanbul, zzgl. MwSt., Fracht und Zoll. Umgerechnet vom TRY-Listenpreis zum angegebenen Kurs; verbindlich erst im Angebot.
Kurs vom: 2026-09-15
A heating control panel starts and stops the heating cable automatically according to weather and surface conditions. Temperature — and, on Proline and Maxline, moisture as well — is read from a sensor, and the system comes on only when needed. There is no switching on and off by hand, no circuits left running and no wasted energy. A heating control panel is mandatory in roof, gutter, ramp, under-concrete and heat trace applications; an installation without a panel falls outside the warranty.
Prevents water, fire, process and plumbing lines freezing, or holds the liquid at a target temperature. The sensor is fitted to the pipe surface. Panel code HMX.
Prevents snow and ice on ramps, car park entrances, footpaths and open slabs. Works with ground surface temperature and moisture sensors. Panel code SMX.
Prevents icicles and blockages forming in gutters, downpipes and along eaves. Works with roof surface temperature and moisture sensors. Panel code RMX.
A heating control panel is built with different sensors and control logic according to the system it controls. Make your choice according to what you are heating.
| Property | Value |
|---|---|
| Mains voltage | 230 Vac 50 Hz · 380/230 Vac 50 Hz, 3PH/N/PE |
| Temperature range | User programmable (factory setting +2 °C) |
| Temperature sensor | Ekoline · Proline: 10K NTC, IP65, −30 / +90 °CMaxline: Eberle TFD 524 004 or TFF 524 002 |
| Moisture sensor | Proline: HTEC/S, −30 / +65 °CMaxline: Eberle ESD 524 003 or ESF 524 001 |
| Protection class | IP65 |
| Enclosure material | Plastic, white |
| Installation | Indoor |
| Ambient operating temperature | +5 / +35 °C |
| Circuit breakers | Type C per heating circuit, 16 / 25 / 40 A |
| Residual current device | 30 mA — Proline and Maxline |
| Wiring | Factory wired, panel with access space |
| Certification | CE |
The heating control panel is built and tested at the factory before dispatch. The work on site consists of hanging the panel on the wall and making the connections.
A heating control panel starts and stops the heating cable automatically according to weather and surface conditions. Temperature — and, on Proline and Maxline, moisture as well — is read from a sensor, and the system comes on only when needed. There is no switching on and off by hand, no circuits left running and no wasted energy. A heating control panel is mandatory in roof, gutter, ramp, under-concrete and heat trace applications; an installation without a panel falls outside the warranty.
Eberle DIN-rail thermostats are control units that manage snow and ice melting and frost protection heating automatically.
The Eberle temperature and moisture sensor is the component that decides when a snow melting or de-icing system runs.
A heat trace junction box is the point, exposed to outdoor conditions, where the heating cable is connected to the supply.
Self-regulating heating cables are cut to length on site.