Pipeline Frost Protection System
A pipeline frost protection system keeps a line working through the winter by running a heating cable along the outside of the pip

SMax is a constant-wattage pipe heating cable made to prevent pipelines from freezing and to hold the liquid at its working temperature.
Richtpreis ab Werk Istanbul, zzgl. MwSt., Fracht und Zoll. Umgerechnet vom TRY-Listenpreis zum angegebenen Kurs; verbindlich erst im Angebot.
Kurs vom: 2026-09-15
SMax is a constant-wattage pipe heating cable made to prevent pipelines from freezing and to hold the liquid at its working temperature. Its difference from self-regulating cables is this: SMax delivers the same wattage to every metre of the run and does not change its output with the ambient temperature. It is therefore the choice on projects where the specification calls for a particular W/m figure, and on long straight runs. It is made in 20, 30, 40 and 50 W/m power options, all four at the same price. A control panel is mandatory — because the cable does not throttle itself, the panel manages the temperature.
SMax is a constant-wattage pipe heating cable of parallel construction. Two supply conductors run side by side along the cable; resistance sections connected between them at set intervals produce the heat. Because each section delivers the same power on its own, the wattage does not change along the run — the first metre of the cable and the thirtieth produce the same heat.
The project calculation becomes simple: total power = metres × W/m. If the specification calls for a particular W/m figure, this cable delivers that figure directly and it can be documented.
The output varies with the ambient temperature and the cable may be overlapped. It is the choice on irregular runs with a high density of valves and flanges.
| Property | Value |
|---|---|
| Type | Parallel, constant wattage |
| Output | 20 · 30 · 40 · 50 W/mall four at the same price |
| Conductor cross-section | 2×0,75 mm² · 2×1,5 mm² · 2×2,5 mm² |
| Supply voltage | 230 V standard115 V and 400 V optional |
| Insulation | Silicone insulation, PVC outer sheath, twin-conductor |
| Behaviour in a fault | Only the damaged section stops heating; the run keeps working |
| Cutting on site | Yes — cut to any length required |
| Overlapping | None |
| Fastening | Integrated cold lead |
| Control | Control panel mandatory |
| Maximum run per circuit | 50–60 mabove this, the circuit is split into several runs |
| Explosion protection | None |
| Conformity | CE-certified manufacture |
| Warranty | 2-year manufacturer warranty |
| Pipe | Diameter | Recommended output |
|---|---|---|
| Plastic (PVC, PPRC, PE) | Up to Ø50 mm | 20 W/mthis figure must not be exceeded |
| Metal | Up to Ø50 mm | 20–30 W/m |
| Metal | Ø50–100 mm | 30–40 W/m |
| Metal | Ø100 mm and above | 40–50 W/m or a twin run |
ISITMAX has manufactured electric heating products in its own facility since 1995; the manufacture is CE-certified. The concept of electrical resistance is a good starting point for classifying heating cables in general: in constant-wattage cables the heat is released across sections of fixed resistance.
A pipeline frost protection system keeps a line working through the winter by running a heating cable along the outside of the pip
Industrial tank heat tracing is a heating cable system wrapped around the body of storage and process tanks: it prevents the liqui
A silicone-insulated pipe heating cable (heat trace) is a heating cable wrapped around or run along the surface of pipe and tank l
HMax is a self-regulating heating cable made to prevent pipelines freezing.
Beschreiben Sie die Anwendung — wir legen das System aus und erstellen ein Angebot.